Boiler Specifications
Utility Boilers
Make/Type/Capacity/Furnace Type/No of Burners & Type/Heating Surface,Furnace Width & Depth/Total Nos : BHPV (1) & BHEL(2)/Natural Circulation,Bi-drum,Front-Wall Fired/Forced Draft,Radiant,Closed bottom, Oil/Gas Fired/4 & Low Nox Burner/3844 m2 m2,5283 mm & 7925 mm /3(UB#1,2&3)
Governor : Woodward
DCS : Centium XL , BlueStar Yokogawa
PLC : Allen Bradley & Modicon
Fire Alarm System : Tata HoneyWell
Economizer : Bare tube Line Economizer
Super Heater : Type /Heating Surface :Platen Type/129 m2
Final Super Heater : Type /Heating Surface : Final/ 493 m2
Attemperator : Type / No of Stage / Medium Sprayed : Spray /1/BFW
Fuel Burning Equipment
Fuel/Capacity (Max/Min) : Rich gas / 2433 kg/hr,634 kg/hr
Oil Burning Equipment
Fuel/Capacity (Max/Min) : SPBS (Special Boiling Point Solvent),Blended Fuel Oil / 1125 kg/hr,705 kg/hr
Steam Drum
No of Tubes /No of Cycles / No of Cyclone Seperators : 672 / 120 / 24 (12x 2 rows)
Steam Quality
VHP HP SLMP LP
Pressure (kg/cm2) 105 40 9 4
Temperature(°c) 505 370 190 170
Steam Turbo Generators
STG # 1
Make/Type/Power Generation Capacity /No of Stages /RPM : BHEL/ Back Pressure & Extraction Type/ 15.5 MW/19/8500
STG # 2
Make/Type/Power Generation Capacity /No of Stages /RPM : BHEL/ Condensing Type/25.6 MW/45/3200
Boiler Equipments
BFW Pump
Make /Capacity /No of Stages/RPM/Total Nos : KSB Pumps Ltd /176 m3/Hr/ 19/2980/2
Make /Capacity /No of Stages/RPM/Total Nos :Sulzer Bingham Pumps Inc/176 m3/Hr/17/2980/1
BFW Turbine
Make/Capacity/RPM/Total Nos : Shanti Gears Ltd/176 m3/Hr/3120/2
Scan-air Fan
Make/Type/Capacity/RPM/Total Nos : Industrial Machinery Pvt Ltd/Centrifugal/1200 m3/Hr/2860/3
Forced Draft Fan
Make/Type/Capacity/RPM/Total Nos : Andrew Yule & Co/Centrifugal Backward Curved Aerofoil/46.5 m3/s/1480/3